Input Voltages
Transformers are dual wound for either 120, 208, 240 volts (+10%, -12%) or for 480 volts, single phase, 60 Hz (+/- 3hz). ARE-M13050 is wound for 208, 240, and 480 volts).
Regulation
DC voltage is maintained within +/-0.5% at any load from no load to full load with+10%,-12% variation (or ANSI standard ranges) in the AC input voltage while floating rated number of cells. Control is accomplished with a single microprocessor-control board and can operate with or without a battery.
During operation, the maximum output voltage transient does not exceed 6% of the initial steady-state voltage for sudden load changes between 10% and 90% of rated output. Recovery takes less than 300 milliseconds. Operation without a battery is stable under all conditions of line and load (within stated limits).
Turn-on under all conditions of line and load has a “soft-start” characteristic with overshoot.
Electrical Noise
For 24 and 48-volt models, the filtering provided produces a ripple level of less than30 millivolts RMS with electrical noise less than 22 dBrnc measured on a battery with an eight-hour capacity rating of four times the rectifier current rating.
For 130-volt models, the filtering provided produces a ripple level of less than 100 millivolts rms when connected to a battery with an eight-hour capacity rating of four times the rectifier current rating.
The total dynamic response of the control circuitry permits all Micro ARE rectifiers to operate as power supplies.
Current Limiting Circuit
The current limiting circuit is factory set at110% of rated DC output but can be adjusted down to 80% and up to 110%.
Float and Equalize Voltages
Both the float and equalize voltages are user adjustable to accommodate different battery types. Float voltages are adjustable from 2.00 -2.32 Volts per Cell and the Equalize voltage is adjustable to a maximum of 2.45 Volts per Cell.
(24V models: 24-28VDC; 48Vmodels: 48-59VDC; 130V models: 120-147VDC)
Temperature Compensation
The user-adjustable temperature compensation circuit will correct float and equalize voltages up to 2.0 mV per cell per °C [added for temperatures below 77°F (25°C) and subtracted for temperatures above 77°F (25°C)]
Ambient Operating Temperatures
All Micro ARE rectifiers will operate at 110% of rated DC output, continuously in temperatures from 32°F to 122°F (0°C to 50°C) up to an altitude of 3,000 ft (1,000 m). De-rating of3.6°F (2°C) for every 990 ft (300 m) over3,300 ft (1,000 m) above sea level. These units can be safely stored for up to 1 year at temperatures ranging from -40°F to 185°F (-40°C to 85°C).
Battery Eliminator Operation
All Micro ARE rectifiers will operate as a power supply without a battery at the following ripple levels:• 24 and 48-volt models less than 30 mV rms• 130-volt models less than 100 mV rms
Circuit Protection
- A shunt-trip AC circuit breaker is provided for input protection
- DC output circuit breaker
- An AC power failure alarm relay provides one set of Form C contacts that operate in case of an AC failure